The main structure of the outdoor cabinet adopts the metal column frame structure, and the roof of the outdoor cabinet can bear the uniformly distributed load of no less than 1kn / m2; The height of the outdoor cabinet base is 200mm, and the base panel is made of plates with a thickness of no less than 3.0mm. After welding, the whole is subject to anti-corrosion surface treatment, and baffles are installed around the base to prevent animals from invading.
Single cabin outer cabinet is a base station construction mode in which communication equipment, power supply equipment, monitoring equipment and battery equipment are installed in the cabin. According to the requirements of floor station and ground station, single cabin cabinet L1 is suitable for floor station with internal dimension of H1400 * w900 * d900mm, and single cabin cabinet D1 is suitable for ground station with internal dimension of h1800 * w900 * d900mm. The single cabin mode is generally used in the construction scenario to meet the one system needs of 1 ~ 2 operators, and 1p split base station air conditioning is adopted. The cabinet outside the two cabins is a base station construction mode in which communication equipment, power supply equipment, monitoring equipment and storage battery are installed in different cabins. The two compartment cabinet (L2) mode is generally applied to the construction scenario of roof stations that meet the one system needs of 1 ~ 2 operators. Three compartment cabinet is composed of two equipment compartments and one integrated compartment. The compartments are interconnected and share an air conditioning system. The three cabinet mode is generally used in construction scenarios that meet the two system needs of 2 ~ 3 operators. The third compartment cabinet (L3) is used for the construction scene of the floor station, the third compartment cabinet (D3-2) is used for the construction scene of the ground station, and the third compartment cabinet (d3-1) is used for the construction scene of the ground station. The fourth compartment cabinet is composed of three equipment compartments and a comprehensive compartment. The compartments are connected with each other, share an air conditioning system, and have the function of opening the door. The four compartment cabinet (D4) is used in the construction scenario to meet the multi system and multi traffic needs of three operators. It can be constructed in the area with large equipment installation demand and limited station area or in case of emergency in the construction cycle. It is mainly used in the construction scene of ground station.
Recommended configuration:
Serial number | Product name | Specification and model |
1 | Integrated cabinet and equipment cabinet | A. External dimension of single cabinet: h * w * D 2000 * 2150 * 1000mm B. Internal dimension of single cabinet: h * w * D 1800 * 2050 * 900mm C. Cabinet composition: cabinet body + cabinet door + base + top cover + rack + cabinet lock D. Cabinet type: 1 unit, 1 cabin, front three doors E. Cabinet material: Frame + insulation cotton material F. Thermal insulation performance: thermal conductivity < 0.472w / (m2. K)
G. Equipment rack: indoor and outdoor units with air conditioner in the left cabin, and equipment cabin in the middle cabin and on the right; H. Cabinet base: 200mm high, 2.0mm thick 1. Incoming mode: bottom in and bottom out Φ 50*4 J. Anti theft design: embedded door, embedded hinge and 3-point anti-theft lock K. Protection grade: IP55 50. Color: ral7035, professional outdoor powder spraying M. Including 2 auxiliary direct fans, grounding copper bars and LED lights, N. Side plate sign "danger of electricity" |
2 | air conditioner | TC06-1.5P ASCinput voltage:AC220V/50Hz |
3 | distribution | 4U AC power distribution: oil engine interlock 63A / 4P * 2; Three phase class B lightning protection; 63a3p * 1, 32A / 1p * 2, 16a / 1p * 2, 10a / 1p * 2, 10a maintenance socket |
4 | ET-PS48200E-6U | Standard 19 inches, embedded frame 6U high; AC input 380V, DC output 48V; Equipped with 50A rectifier module * 3 and monitoring management module * 1; Have battery charging management; Power distribution part: AC input: air switch dz47-63 / 4 C63 63A / 4P * 1; Three phase AC class C lightning arrester 20 ~ 40ka; AC output: air switch dz47-63 / 2 C32 32A / 2p * 1; Ground wire terminal * 1; DC class C lightning arrester 20 ~ 40ka 1p * 1; DC output: primary power down: dz47-125 / 1 100A / 1p * 2, dz47-63 / 1 C32 32A / 1p * 2; Secondary power down: dz47-63 / 1 C63A / 1p * 4; Battery air switch: dz47-125 / 1125A/1P *2。 |
5 | Lead acid battery | 12V50AH(16PCS) |
6 | Moving ring monitoring | 1U moving ring monitoring host + smoke sensor + water immersion sensor + access control + temperature and humidity sensor |